Chapter XIII: Appendix: No. 4
SUBMARINE MINE CABLE.
Submarine mine cable is shipped on reels having an outer sheathing for protection in transit, with at least 12 feet of both ends of the cable brought out and coiled on the head of the reel for test purposes. If the cable is not for immediate use, it should be moved to the cable tank, and by means of the overhead trolley and cable tongs put in its position in the tank, the two ends being properly tagged and firmly fixed so as to allow it to be tested. In arranging the multiple cable in the tanks that which is to be used first should be most readily accessible.
The cable tank should be provided with a cover to keep it clean, as well as to lessen as much as possible variations of temperature. Enough clean water to cover by several inches the outer sheathing of the cable reels should be kept in the tanks, but in climates where the water in the cable tanks would normally freeze to a depth exceeding 2 feet, the water should be let out of the tanks before ice begins to form and not again admitted until the following spring. In localities where the tanks may become a breeding place for mosquitoes, as a preventive measure, salt water from the ocean or bay should, when practicable, be used for filling the tanks, or where it is necessary to use fresh water sufficient salt should be added to produce a 3 per cent solution. No oil or kerosene should be used in the tanks.
The methods of recording tests and of classifying and transferring submarine mine cable are prescribed by orders from the War Department. The tests of submarine mine cable at posts will consist in determining the insulation and conductor resistances.
The insulation surrounding the conductor of a cable is supposed to be uniform in regard to quality of material, density, and thickness. The resistance which it offers to the passage of a current through it will then vary inversely with its length. In comparison the insulation resistance of 1 mile of cable is taken as the standard. This insulation has a large negative temperature coefficient; that is, an increase of temperature lowers its resistance. It is customary to reduce all insulation resistance to that at a standard temperature of 60° F., and for this purpose reduction factors applicable to the particular insulation compound should be furnished with the cable. (Note: It has been found that for most compounds, if the logarithms of the resistance are plotted as ordinates against the temperature in degrees F. as abscissæ, the resulting curve will be very nearly a straight line.)
The ordinary methods of measuring resistance—that is, by means of a Wheatstone bridge, or by fall of potential, or by voltmeter—can not be used in measuring resistance as high as that of the insulation of a submarine cable. For this the direct deflection method is employed.
In brief, this consists of the following steps:
First. The deflection produced in a galvanometer by a current from a battery through a known resistance, usually 100,000 ohms, is determined, whence is calculated the resistance through which this same battery would produce a deflection of one point using the unity shunt. This is expressed in megohms and is called the galvanometer “constant” under the conditions.
Second. The deflection produced by the current from the same battery through the insulation of the cable is determined, whence, from “First,” the corresponding number of megohms is calculated.
Third. This multiplied by the length of the cable in miles and corrected for temperature gives the required insulation resistance per mile.
This testing can be made most satisfactorily on dry days, but a close adherence to the instructions herein given relative to the preparation of the cable ends, the insulation of the cable lead and of the battery, and the drying out of the test room and instruments should enable satisfactory work to be done under adverse conditions of weather or climate. The following apparatus is required: Reflecting galvanometer, universal shunt, special testing key, 100,000-ohm resistance box, battery of dry cells giving approximately 100 volts, and stop watch.
Figure 16 shows diagrammatically the arrangement of the apparatus for testing a reel of cable. As a rule the instruments should be so placed that one person may manipulate the key and the shunt while at the same time observing the galvanometer.
The 100,000-ohm box, as a protection to the galvanometer in testing, is always kept in the circuit and its value should be subtracted from the resistance determined, except in the case of high insulation resistance when it will not be necessary to make the subtraction.
The universal shunt is always employed with the galvanometer and is used both to vary the current through the latter and to protect it from a violent throw at the instant of making or breaking the circuit at the testing key. This last is accomplished by having the shunt on zero at such times.
The galvanometer being a very sensitive instrument must be solidly supported so as to be free from jars or vibrations.
The special testing key, shown diagrammatically in the figure, has its binding posts plainly marked. It is a double-throw key and has two positions upon each side. When completely closed to the right, the cable is charged through the galvanometer from the positive pole; when to the left, from the negative pole of the battery. In each case the deflection of the galvanometer is in the same direction. When partly closed on either side, the cable is discharged to earth through the galvanometer. (Note: It will be observed that the connections are such that the galvanometer is always connected to the cable core and never to the ground. With this connection, _so long as the lead PX is free from leaks or grounds_, the galvanometer measures only the current actually passing through the core and not that leaking through any imperfect insulation in the battery and leads.)
Cable testing is a very simple operation, but extreme care is necessary in all operations.
The following is a detailed description:
=I. Preparing the cable for testing.=—1. Closely examine each conductor end. Look particularly for unusually hard or brittle insulation and for torn, pinched, or punctured insulation, especially near the ends of the armor wires. If any of the ends are not in perfect condition, cut off enough cable to secure good ends. (_Caution._—Do not cut off more than enough to secure good ends, for after three or four tests it may be necessary to unreel the whole cable to secure enough of the inner end above water.)
2. Verify the tagging. Remember that the “shore end” is the end from the outer coils on the reel and is numbered clockwise. The other end is numbered contraclockwise.
3. The “ground” should be made by taking several turns of bare copper wire around the armor of the cable to be tested and soldering them in position. One such ground in each tank is sufficient. Whenever “ground” or “earth” is subsequently spoken of, this ground in the tank is meant, and not a connection to ground at some point outside the tank.
4. The leads PX and BY (fig. 16) should be of loading or other heavily insulated wire. They must be carefully insulated from each other, from the ground, and from the walls or other parts of buildings. This is especially true of the cable lead PX. In damp weather porcelain-knob insulators and porcelain tubes (the latter for use in passing through walls or partitions) may not be sufficient to afford proper insulation for the cable lead. In such case the latter should be suspended _in the air_ from the testing switch to the cable tank by means of several chains of paraffined porcelain insulators suspended by marline or protective tape which has been boiled in paraffin. These suspensions should be in each case under cover and should be kept as dry as possible. The length of the leads is immaterial. If loading wire is used, the distance between supports should be short (not over 50 feet), as this wire stretches considerably from its own weight, pulling out the insulation and giving a very thin wall, particularly at points of support. Extreme care should be taken to tighten up on the knob insulators, in case they are used, just enough to hold the wire without pinching the insulation.
5. Using a double connector, join the lead BY to the ground wire on the cable above the surface of the water. Put a connector on the end of the other lead so that it can be readily attached in turn to each conductor.
6. Any protective covering, such as armor, jute, etc., should be removed from the ends of the conductors for a distance of about 12 inches, thus laying the insulation coating bare. This latter should not be handled and must be kept scrupulously clean. With a _clean dry_ knife prepare each conductor of the cable to be tested by cutting off about 1 inch of the insulation from each end of the wire and then tapering the end of the insulation for about 1 inch, leaving a perfectly clean surface. In damp weather dip each end of each conductor into melted paraffin (not boiling, but heated above 212° F.). Secure one end of the cable so that it is well separated from the surrounding objects and separate the conductors so that no ends are touching.
7. Take one strand of a loading wire about 4 feet long and wrap it two or three times around the projecting copper end of each conductor at the other end of the cable, then connect it to earth. See that the conductors at this end are dry. Leave the lead PX disconnected and suspended in the air.
=II. Setting up the testing apparatus.=—1. Select a light, dry room as near the cable tank as practicable.
2. Use dry cells for the battery. The voltage of the battery should be such as to give a full scale deflection of the galvanometer through the resistance employed for taking the constant (with shunt at ¹/₁₀₀₀). Large galvanometer throws are essential for reliable results.
Set up the cells on shelves in a small closed closet or box, with narrow strips of wood or heavy cardboard laid between each row of cells, lengthwise and crosswise. The height of each strip should be about half the height of a cell, so that the two layers of strips will come nearly to the tops of the cells and keep them well separated. Wire the cells in series and bring the terminals out to a double-pole single-throw switch, which should be on a heavy porcelain or slate base and rated for at least 250 volts. (It may be found desirable to install some electric lamps in the closet to keep the battery dry.)
If difficulty is experienced in eliminating grounds from the battery set up in this manner, the battery box should be suspended in air by means of chains of paraffined cleats.
3. Set up the galvanometer on a pier or on a window sill if the building is of masonry. It should be insulated by placing its feet on a slate or ebonite slab, or in glass insulators. Remove the cover. Adjust the level until the suspended coil hangs freely. Maneuver the suspended coil, by means of the knob at the top of the tube, until its face is parallel with the face of the instrument. Then adjust the level until the upper suspension hangs in the center of the supporting tube, and the air gap between the coil and armature is symmetrical. Replace the cover. Put on the scale and the telescope. Turn the mirror so that it reflects the 0 of the scale approximately, getting exact adjustment by moving the scale. Be careful (particularly in dry weather) not to touch the glass of the cover or to do anything which will produce a static charge on the glass.
The galvanometer scales are usually graduated in equal divisions corresponding to 1 millimeter on the circumference of a circle whose radius is 1 meter. Each tenth division is usually marked with a number. This number is sometimes 1 instead of 10, 2 instead of 20, and so on. The number of divisions to read and record is the number of smallest (millimeter) divisions. Do not try to read closer than ½ of one division. The larger the throw the less the personal error. No accurate conclusion can be drawn from a very small throw.
4. Place a table or low shelf conveniently to one side and place the shunt, the testing key, the ⅒ megohm box, and a voltmeter on it. The apparatus should be insulated by an ebonite or slate slab, or glass insulators. Fasten the shunt and the key securely to the table or the shelf. (The use of paraffin paper for insulating instruments is a makeshift at best. It soon gets soiled and creased, then it has to be replaced.)
The use of lamps to keep the apparatus dry may be desirable, or it may be found convenient to expose the apparatus to the sun for a few minutes before beginning the test on any day. The use in the testing room of a small stove or of a gasoline torch for two or three hours before the beginning of the testing will ordinarily prove very advantageous.
5. Wire up as in figure 16, except that the leads from the testing key should be carried to the battery through the double-pole single-throw switch above referred to. (The battery switch should be opened whenever any connections are made or altered.) All leads used in connecting up the instruments should be of heavy copper, and stiff enough to hold permanently any shape to which they are bent. They should be supported at points of connection only, and should not lie on the table or within an inch of each other.
=III. Testing the insulation of the apparatus.=—1. _Voltmeter test of battery insulation._—This is a rough test, but should be included. A serious ground can be much more quickly located with a voltmeter than with the galvanometer.
(_a_) Disconnect the battery leads at the battery switch; connect + lead of battery to + post of the voltmeter; connect the B end of the lead BY to - post of the voltmeter; - lead of the battery should be in the air. Close the voltmeter switch and read.
(_b_) Disconnect the voltmeter. Connect - lead of the battery to - post of the voltmeter. Connect the B end of the lead BY to + post of the voltmeter; + lead of the battery should be in the air. Close the voltmeter switch and read.
If any deflection is obtained in either case, the battery or its connections are grounded. Locate and remove the ground. (See Foster or some other practical handbook.)
2. _Testing the battery voltage._—Connect the voltmeter across the battery terminals. Read and record the voltage. (If there is no voltmeter available which will read as high as the battery voltage, take the voltage of the battery in sections and add, or make a multiplier of one of the resistance coils in the ⅒ megohm box.)
3. _Testing the battery and the apparatus for grounds with the galvanometer._—With a camel’s-hair brush go over all the instruments and carefully remove dust. See that the instruments and connections are dry. Do not blow on the instruments.
Open the battery switch. Connect the battery leads to the battery switch. Disconnect lead PX at P and connect the earth leads BY and EY to the key at “_cable post_.” (Y is grounded.) _Both_ battery leads are left connected to the key. The shunt should be on 0. Close the battery switch. Close the testing key to the right. Turn the shunt gradually to the unity post. The galvanometer deflection should be zero. Turn the shunt to 0. Reverse the testing key. Turn the shunt to the unity post. The deflection should be zero. If any deflection is obtained, there is a ground in the battery, the apparatus, or the connections. The test of the cable should not proceed if a deflection is obtained in either position of the key.
In reporting the voltage + to earth and - to earth as “zero” on form, it will be understood that this means zero using the galvanometer, as herein described.
4. _Insulation of leads._—Turn the shunt to 0. Open the battery switch. Connect the earth leads BY and EY to their proper posts. Connect the cable lead, PX, to “cable” post. See that the cable tank ends of the lead PX is disconnected at X and suspended in the air. Close the battery switch. Close the key and turn the shunt to the unity post. Deflections should be as small as possible and in any case _must be steady and uniform for several trials_. Turn the shunt to 0. Reverse the key, stopping at the discharge position. Turn the shunt to the unity post and wait until the galvanometer rests at 0, indicating that the leads are discharged. Turn the shunt to 0. Close the key all the way down. Turn the shunt to the unity post. The deflection should not differ materially from that noted above. If there is a deflection, the trouble is in the lead PX or its connections. Go over these, carefully examining for dust and moisture and noting particularly the proximity of all wires of opposite potential which cross or lie near each other. If there is a small deflection which can not be removed, a correction must be applied subsequently to the deflection obtained in the test for the insulation resistance of the conductor.
Using proper care, there are very few days when perfect insulation of the instruments can not be secured. The lead leakage with well-insulated wire put up properly will be noticed rarely.
5. _Use of Price guard-wire._—As an additional precaution against surface leakage across the insulation at the ends of the conductor it will sometimes be advisable to install an additional lead (not necessarily as carefully insulated as PX) running from the testing switch to the cable under test. This lead should be connected in at the testing switch to the post carrying the lower blade between “D” and “C” (fig. 16); the tank end should be bare of insulation for a sufficient distance to enable the bare wire to be wrapped firmly, without pinching, around the insulation at each end of the particular conductor under test, just below the tapered portion.
The potential difference between the cable core and this guard-wire is thus made practically nil, so that any leakage will be from the guard-wire to the tank, consequently this leakage will not be measured by the galvanometer.
=IV. Take the galvanometer constant as follows=: Open the battery switch.
With a short piece of wire connect the hinge post of the testing key marked “cable” to either “earth” post of the key, the leads to the cable tank being disconnected at E, B, and P. Turn the shunt to 0. Examine the ⅒ megohm box and see that all the resistance coils are in the circuit. Close the battery switch and the testing key. Turn the shunt to the ¹/₁₀₀₀ post. Watch the swing of the galvanometer and when it has come to rest, read and record. Turn the shunt to 0. The galvanometer should return exactly to 0. If it does not, readjust and repeat until it does. The galvanometer constant is numerically equal to the total throw in _smallest_ divisions of the scale multiplied by 100. Remove the connecting wire and replace the leads to the tank.
If at any subsequent time during the test the galvanometer adjustment is disturbed—that is, if it does not return accurately to zero when the shunt is at 0—the constant should be redetermined.
=Testing the cable.=—1. See that the testing key is open and the shunt at 0. Connect the earth lead to ground on the cable armor. Remove the earth connection from No. 1 conductor and connect the cable lead to this conductor; in wet weather the connector joint should be dipped in melted paraffin. (In using paraffin to insulate joints or ends bring it just above 212° F. to evaporate any moisture present. It should not be boiling. The paraffin coating should be at least as thick as the rubber insulation and extend back over the rubber for an inch or more.)
2. Close the testing key to the left (+ to earth), stopping at the discharge position, and turn the shunt to the unity post. There should be no deflection. If there is, it is due either to a charge on the cable, which will disappear after a moment, or to earth currents. (It is assumed that the testing apparatus has been thoroughly tested for insulation.) If due to earth currents, the conductor is probably a poor one. Earth currents are readily recognizable by their fluctuating character. Before assuming that the trouble can not be removed, the joint between the lead and the conductor should be examined again. Moisture on the cable end will give a path for earth currents. Note the value and direction of the throw of the galvanometer and record it.
3. Turn the shunt to 0, close the testing key all the way down (+ to earth), noting the time to the second, or starting the stop watch at the same time, if one is available. The time must be accurately noted. The insulation resistance at the end of one minute’s electrification is the resistance to be reported.
4. When 35 seconds have elapsed, turn the shunt to the ¹/₁₀₀₀-post and watch the galvanometer throw; if small, move the shunt successively to the ¹/₁₀₀-post, to the ¹/₁₀-post, and to the unity post. This operation must be completed before 45 seconds have elapsed from the time the key was closed. With good cable the unity post will always be reached without danger of throwing the galvanometer reading off the scale. Remember that each successive post should give 10 times the throw of the preceding post.
5. At the end of one minute read the deflection, correct for the leakage of the leads and the earth currents, and record. (See example following.)
6. At the end of two minutes read the deflection, correct and record it. For good cable it should be less than the deflection observed at the end of one minute.
7. Turn the shunt to 0, and reverse the key, stopping at the discharge position. Turn the shunt on gradually until the unity post is reached and wait until the reading is 0, indicating that the conductor is discharged. If earth currents are present, 0 will not be reached or will be passed. In this case proceed as before described. A submarine mine cable conductor a mile long will discharge ordinarily in about three minutes.
8. Turn the shunt to 0, stop and start the stop watch; at the same time close the key all the way down (- to earth).
9. After 35 seconds, start turning the shunt, ceasing at 45 seconds. (See paragraph 4, above.)
10. At the end of one minute read the deflection, correct and record it. For good cable it should be substantially the same as the deflection observed at the end of one minute with + of the battery to earth.
11. Turn the shunt to 0, and reverse the key, stopping at the discharge position.
12. Disconnect No. 2 conductor from ground. Disconnect No. 1 from the lead and connect up No. 2. Connect No. 1 to ground. It is not necessary to wait for No. 1 to be discharged completely before disconnecting it.
13. Proceed with No. 2 as with No. 1 and repeat with each conductor.
14. On the completion of the test all conductor ends should be carefully taped.
15. To determine the correct value of the insulation resistance it is essential that the negative pole of the battery be connected to the core of the cable, otherwise the products of electrolysis will tend to seal up any fault which may exist and will cause the conductor to appear better than it really is. With the negative pole of the battery to the core the tendency is to deposit copper on the core and thus to lay bare any fault. The insulation resistance of any conductor is therefore found by multiplying the corrected deflection at the end of one minute, with + of battery to earth, by the denominator of the shunt used, and then dividing the galvanometer constant by this product. The resistance of the ¹/₁₀-megohm box is neglected unless the insulation resistance determined is very low, say, under 1 megohm, when the 100,000 ohms should be subtracted from the above quotient.
16. To determine the insulation resistance per mile at 60° F., multiply the actual insulation resistance found by the length of the cable in miles, and this result by the multiplier furnished by the torpedo depot for the particular make of cable, corresponding to the temperature of the water in the tank observed during test.
_Example._—Leakage of the leads found to be one-half division. Earth currents found to give 1½ divisions in a negative direction from 0 of the scale. Galvanometer throw at the end of one minute (+ to earth), 15 divisions. The corrected deflection is, 15 - ½ + 1½ = 16 divisions.
The galvanometer constant (450 divisions through ¹/₁₀ megohm, shunt at ¹/₁₀₀₀), 45,000 megohms. That is, the battery will give ¹/₁₀ of 450 divisions = 45 through 1 megohm, the shunt at ¹/₁₀₀₀; or, what is the same thing, one division through 45 megohms, the shunt at ¹/₁₀₀₀; therefore with the shunt at unity the battery will give one division through 45 × 1,000 = 45,000 megohms. The insulation resistances = 45,000 ÷ 16 = 2,813 megohms. If the cable is three-fourths mile long, the insulation resistance in megohms per mile is 2,813 × ¾ = 2,110 megohms.
Manufacturer, Safety Insulated Wire & Cable Co.
Temperature of water in tank, 80° F.
Multiplier, 1.7056; 2,110 × 1.7056 = 3,599 megohms insulation resistance per mile at 60° F. This result is recorded on the form.
=VI. Copper resistance.=—1. The drop of potential method is quicker than the bridge method under the usual conditions and should be used if the apparatus is available.
_Apparatus required._—(_a_) Source of power (110 volts D. C. lighting circuit, casemate battery or generator); (_b_) a double-pole single-throw switch to which the power leads are attached; (_c_) a bank of ten 110-volt lamps in parallel; (_d_) a D. C. ammeter of not more than 0-25 scale; (_e_) a D. C. voltmeter, 0-150 scale.
Place the lamp bank and the ammeter in one side of the power line from the switch to the conductor, and the other end of the conductor to the other side of the power line. Connect the voltmeter across the ends of the cable so as to measure the drop of potential between the ends of the conductor being tested. Close the switch, take simultaneous readings on the voltmeter and the ammeter and calculate the resistance. With the apparatus described a conductor 1 mile long will receive about 2½ amperes and show a drop of about 50 volts. The lamps are inserted as a safety precaution. In no case should the current through the conductor exceed 6 amperes. If the cable has been tested for insulation resistance and all the conductors show high insulation, the lamps are not necessary, provided the cable is at least a mile long.
2. The copper resistance found is reduced to that at 60° F. by multiplying by the coefficient found in the following table with the temperature of the water in the tank at the time of the test as an argument:
_Reduction of copper resistance to 60° F._
+--------------+--------++--------------+--------+
| Temperature. | δ || Temperature. | δ |
+--------------+--------++--------------+--------+
| _°F._ | || _°F._ | |
| 10 | 1.1252 || 55 | 1.0113 |
| 11 | 1.1224 || 56 | 1.0090 |
| 12 | 1.1196 || 57 | 1.0068 |
| 13 | 1.1168 || 58 | 1.0045 |
| 14 | 1.1141 || 59 | 1.0023 |
| 15 | 1.1113 || 60 | 1.0000 |
| 16 | 1.1086 || 61 | .9978 |
| 17 | 1.1059 || 62 | .9956 |
| 18 | 1.1032 || 63 | .9933 |
| 19 | 1.1005 || 64 | .9911 |
| 20 | 1.0978 || 65 | .9889 |
| 21 | 1.0952 || 66 | .9867 |
| 22 | 1.0925 || 67 | .9846 |
| 23 | 1.0899 || 68 | .9824 |
| 24 | 1.0873 || 69 | .9802 |
| 25 | 1.0846 || 70 | .9781 |
| 26 | 1.0820 || 71 | .9759 |
| 27 | 1.0794 || 72 | .9738 |
| 28 | 1.0769 || 73 | .9717 |
| 29 | 1.0743 || 74 | .9695 |
| 30 | 1.0717 || 75 | .9674 |
| 31 | 1.0692 || 76 | .9653 |
| 32 | 1.0667 || 77 | .9632 |
| 33 | 1.0641 || 78 | .9611 |
| 34 | 1.0616 || 79 | .9591 |
| 35 | 1.0591 || 80 | .9570 |
| 36 | 1.0566 || 81 | .9549 |
| 37 | 1.0542 || 82 | .9529 |
| 38 | 1.0517 || 83 | .9508 |
| 39 | 1.0492 || 84 | .9488 |
| 40 | 1.0468 || 85 | .9468 |
| 41 | 1.0443 || 86 | .9448 |
| 42 | 1.0419 || 87 | .9428 |
| 43 | 1.0395 || 88 | .9408 |
| 44 | 1.0371 || 89 | .9388 |
| 45 | 1.0347 || 90 | .9368 |
| 46 | 1.0323 || 91 | .9348 |
| 47 | 1.0300 || 92 | .9328 |
| 48 | 1.0276 || 93 | .9308 |
| 49 | 1.0252 || 94 | .9288 |
| 50 | 1.0229 || 95 | .9269 |
| 51 | 1.0206 || 96 | .9250 |
| 52 | 1.0182 || 97 | .9231 |
| 53 | 1.0159 || 98 | .9211 |
| 54 | 1.0136 || 99 | .9192 |
+--------------+--------++--------------+--------+
The true length of a cable should be that of its center conductor.
From the size of the conductor and its copper resistance the length of the cable may be computed by use of the following wire table:
_Table of resistances of pure copper wire
at 60° F._
+---------+---------+-------------+
| Size | Dia. in | Ohms per |
| B. & S. | mils. | 1,000 feet. |
+---------+---------+-------------+
| 1 | 289 | 0.11999 |
| 2 | 258 | .15130 |
| 3 | 229 | .19080 |
| 4 | 204 | .24058 |
| 5 | 182 | .30338 |
| 6 | 162 | .38256 |
| 7 | 144 | .48245 |
| 8 | 128 | .60831 |
| 9 | 114 | .76696 |
| 10 | 102 | .96740 |
| 11 | 91 | 1.21960 |
| 12 | 81 | 1.5379 |
| 13 | 72 | 1.9393 |
| 14 | 64 | 2.4453 |
| 15 | 57 | 3.0134 |
| 16 | 51 | 3.8880 |
| 17 | 45 | 4.9030 |
| 18 | 40 | 6.1827 |
| 19 | 36 | 7.8024 |
| 20 | 32 | 9.8316 |
| 21 | 28.5 | 12.397 |
| 22 | 25.3 | 15.625 |
| 23 | 22.6 | 19.712 |
| 24 | 20.1 | 24.857 |
| 25 | 17.9 | 31.343 |
| 26 | 15.9 | 39.535 |
| 27 | 14.2 | 49.839 |
| 28 | 12.6 | 62.848 |
| 29 | 11.3 | 79.250 |
| 30 | 10.0 | 99.932 |
+---------+---------+-------------+
The objections to the use of a bridge for measuring copper resistance are the difficulty of eliminating the resistance of the plug contacts and the time required to secure balance. The resistance of the plug contacts may often be as high as 20 ohms, particularly if used at the tank.
If the bridge is used at all, it should be placed in the testing room, and the same leads employed for testing insulation should be used. The resistance of these leads should first be determined by connecting them together and measuring; this resistance is subtracted from each resistance measured.
=VII. General.=—The key to success in cable testing is great care in every detail. The cable now being furnished is all tested with galvanometers having constants from 200,000 to 250,000 megohms. It has all been accepted after most careful test. The chances are that it is good when it arrives at the post, unless it has been mechanically injured in transit, which should be ascertained by careful inspection when delivered at the post.
Do not accept a single measurement if it shows low resistance, but repeat until certain of results. The time between trials on the same conductor should be as great as practicable. For example: Measurements showing low resistance made in the morning should be repeated in the afternoon; those made in the afternoon should be repeated the next day; the conductor being connected to earth during the interval between tests.
Comments
Log in to leave a comment.
Manual for submarine miningChapter XIII: Appendix: No. 4
0%23 min left in chapter